Configuring the display object for the CE360 - Johnson Controls - LIT-12013860 - CE360 Critical Environment Display

CE360 Critical Environment Display Installation Guide

Brand
Johnson Controls
Product name
CE360 Critical Environment Display
Document type
Installation Guide
Document number
LIT-12013860
Revision date
2023-11-08
Language
English

You can configure the display object in CCT to display parameters for multiple rooms. The CE360 display shows a maximum of two rooms with a combined maximum of 10 parameters. For example, there are two zones and each zone has different parameters. The following table explains the steps to configure the display object for CE360.

Table 1. Display object example
Page name Order Read-only Mapping point
R1_PRO_Zone1 1 Yes ZN1-ISOLATION-MODE-LIMIT
2 Yes ZN1-ISOLATION-MODE-S
3 No ZN1-ISOLATION-MODE
4 Yes ZN1-OCCUPANCY MODE-S
5 No ZN1-OCCUPANCY-OVERRIDE
6 No ZN1-CLEAN-EN
7 Yes ZN1-CLEAN-DURATION
R1_TILE_Pressure 1 Yes ZN1-P
2 Yes ZN1P-ALM-EN
3 Yes ZN1P-A
4 Yes EFF-ZN1PSP
5 No ZN1P-SP
R1_TILE_Temperature 1 Yes ZN1-T
2 Yes ZN1T-ALM-EN
3 Yes ZN1T-A
4 No ZN1T-SP
R1_TILE_CO2 1 Yes ZN1-CO2
2 Yes ZN1CO2-ALM-EN
3 Yes ZN1CO2-A
R1_TILE_Humidity 1 Yes ZN1-H
R2_PRO_Zone2 1 Yes ZN2-ISOLATION-MODE-LIMIT
2 Yes ZN2-ISOLATION-MODE-S
3 No ZN2-ISOLATION-MODE
4 Yes ZN2-OCCUPANCY-MODE-S
5 No ZN2-OCCUPANCY-OVERRIDE
R2_TILE_Offset 1 Yes ZN2-CURRENT-VOL-DIFF
2 Yes ZN2-VOLDIFF-ALM-EN
3 Yes ZN2-VOLDIFF-A
4 Yes ZN2-EFFVOLDIFF-SP
5 No ZN2-VOLDIFF-SP