Device Object Type - Johnson Controls - LIT-12012608 - SI-VRFCBN02-0S - SI-VRFCBN02-0SA - SI-VRFCBN02-0SC - SI-VRFCBN02-0SE - SI-VRFCBN02-0SI - SI-VRFCBN02-0SJ - SI-VRFCBN02-0SN - SI-VRFCBN02-0SS - Bulb controller - BACnet VRF Smart Gateway

BACnet VRF Smart Gateway Protocol Implementation Conformance Statement

Product
Network and Communications > Gateways and Routers > BACnet VRF Smart Gateway
Network and Communications > BACnet > BACnet VRF Smart Gateway
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12012608
Revision date
01/01/2018
Property Name Required Optional Writable Property ID Range
APDU_SEGMENT_TIMEOUT     10 1000-65535
APDU_TIMEOUT     11 1000-65535
APPLICATION_SOFTWARE_VERSION     12  
DATABASE_REVISION     155  
DESCRIPTION   28 161 char max
DEVICE_ADDRESS_BINDING     30  
FIRMWARE_REVISION     44  
MAX_APDU_LENGTH_ACCEPTED     62 1024
MAX_SEGMENT_ACCEPTED     167  
MODEL_NAME     70  
NUMBER_OF_APDU_RETIRES     73 4
OBJECT_IDENTIFIER   75 0-4189551
OBJECT_LIST     76  
OBJECT_NAME   77 400 char max
OBJECT_TYPE     79  
PROTOCOL_OBJECT_TYPES_SUPPORTED     96  
PROTOCOL_REVISION     139  
PROTOCOL_SERVICES_SUPPORTED     97  
PROTOCOL_VERSION     98  
SEGMENTATION_SUPPORTED     107  
SYSTEM_STATUS     112  
VENDOR_IDENTIFIER     120  
VENDOR_NAME     121  
Table 1.
Property Name Required Optional Writable Property ID Range
COV_INCREMENT   22  
DESCRIPTION     28  
EVENT_STATE     36  
MAX_PRESENT_VALUE     65  
MIN_PRESENT_VALUE     69  
OBJECT_IDENTIFIER     75  
OBJECT_NAME     77  
OBJECT_TYPE     79  
OUT_OF_SERVICE   81  
PRESENT_VALUE   85  
RELIABILITY   103  
STATUS_FLAGS     111  
UNITS     117