Installing the WRG1830 Wireless Router Gateway - Facility Explorer - LIT-12013796 - Wireless Device - WRG1830/ZFR183x Pro Series

WRG1830/ZFR183x Pro Series Wireless Field Bus for Facility Explorer Systems Technical Bulletin

Product
Document number
LIT-12013796
Revision date
2025-02-07
Product status
Active

About this task

To install the WRG1830 Gateway and connected Coordinator Radio, complete the following steps:

Procedure

  1. Refer to the WRG1830 Wireless Router Gateway (WRG) Installation Guide (Part No. 24-11460-00018) and the ZFR1831 Pro Series Wireless Router Installation Guide (Part No. 24-11460-0004).
  2. Set the ZFR1831 Pro Coordinator Radio’s PAN OFFSET Switch according to the job drawings.
    Important: The PAN OFFSET switch setting must be the same for all the wireless devices on the same wireless mesh network.
    Important: To avoid interference, assign a unique PAN OFFSET to each wireless network in a building. Using a unique PAN OFFSET is particularly important if you have PANs on adjacent floors of a building. Do not use the same PAN OFFSET on multiple wireless networks in a building, even if the PANs do not overlap
  3. Connect the WRG1830 Gateway to an available Ethernet switch or hub port.
  4. Connect the USB Wi-Fi dongle.
  5. Connect the power supply to the WNC1800 Gateway, but do not apply power until commissioning the wireless system.