PCX Series point type counts per model - Facility Explorer - LIT-1900671 - Field Device - FX-PCX17 Expansion Input/Output Module - FX-PCX27 Expansion Input/Output Module - FX-PCX37 Expansion Input/Output Module - FX-PCX47 Expansion Input/Output Module

PCX Input/Output Expansion Modules Catalog Page

Brand
Facility Explorer
Product name
FX-PCX17 Expansion Input/Output Module
FX-PCX27 Expansion Input/Output Module
FX-PCX37 Expansion Input/Output Module
FX-PCX47 Expansion Input/Output Module
Document type
Catalog Page
Document number
LIT-1900671
Revision date
2020-11-23
Language
English
Table 1. FX-PCX Series point type counts per model

Point types

Signals accepted

FX-PCX 1711

FX-PCX 2711

FX-PCX 2721

FX-PCX 3711

FX-PCX 3721

FX-PCX 3731

FX-PCX 4711

Universal Input (UI)

Analog Input, Voltage Mode, 0–10 VDC

Analog Input, Current Mode, 4–20 mA

Analog Input, Resistive Mode, 0–2k ohm, RTD (1k NI [Johnson Controls], 1k PT, A99B SI), NTC (10k Type L, 2.252k Type 2)

Binary Input, Dry Contact Maintained Mode

 

2

8

4

   

6

Binary Input (BI)

Dry Contact Maintained Mode

Pulse Counter/Accumulator Mode (High Speed), 100 Hz

4

     

16

8

2

Analog Output (AO)

Analog Output, Voltage Mode, 0–10 VDC

Analog Output, Current Mode, 4–20 mA

   

2

     

2

Binary Output (BO)

24 VAC Triac

         

8

3

Universal Output (UO)

Analog Output, Voltage Mode, 0–10 VDC

Binary Output Mode, 24 VAC/DC FET

Analog Output, Current Mode, 4–20 mA

 

2

 

4

     

Configurable Output (CO)

Analog Output, Voltage Mode, 0–10 VDC

Binary Output Mode, 24 VAC Triac

           

4

Relay Output (RO) (-0 Models Only)

120/240 VAC

 

2

 

4

     

Relay Output (RO) (-2 Models Only)

24 VAC

 

2

 

4

     
Table 2. PCX Series point type counts per model

Point types

Signals accepted

PCX 2723

PCX 3723

PCX 3733

Universal Input (UI)

Analog Input, Voltage Mode, 0–10 VDC

Analog Input, Current Mode, 4–20 mA

Analog Input, Resistive Mode, 0–2k ohm, RTD (1k NI [Johnson Controls], 1k PT, A99B SI), NTC (10k Type L, 2.252k Type 2)

Binary Input, Dry Contact Maintained Mode

8

   

Binary Input (BI)

Dry Contact Maintained Mode

Pulse Counter/Accumulator Mode (High Speed), 100 Hz

 

16

8

Analog Output (AO)

Analog Output, Voltage Mode, 0–10 VDC

Analog Output, Current Mode, 4–20 mA

2

   

Binary Output (BO)

24 VAC Triac (Ext Power Only)

   

8