N2 Device and point configuration - Facility Explorer - LIT-12012045 - Field Device - N2 Controllers

Modernization Guide for N2 Controllers - Facility Explorer

Product name
N2 Controllers
Document type
User Guide
Document number
LIT-12012045
Revision date
2019-03-22

Legacy VAV1xx controllers identify themselves to their N2 supervisor as a VAV device type. The FX-PCV and FX-PCG support identifying themselves to its N2 supervisor as a VAV device type, which eliminates the need to change this in the N2 supervisor's configuration. To configure this capability, use the N2 Mapping feature of CCT to set the FX-PCV or FX-PCG controller's device type to VAV.

Figure 1. Using CCT to set the FX-PC Controller's device type to VAV

No utilities are available to automatically recreate the N2 Mapping Table, so you must manually recreate it using CCT.