N2 device and point configuration - Facility Explorer - LIT-12012045 - Field Device - N2 Controllers

Modernization Guide for N2 Controllers - Facility Explorer

Brand
Facility Explorer
Product name
N2 Controllers
Document type
User Guide
Document number
LIT-12012045
Revision date
2019-03-22
Language
English

DX-9100 controllers identify themselves to their N2 supervisor as a Sys91 device type. The FX-PCA3611 does not support identifying itself to its N2 supervisor as a Sys91 device type. As a result, you must use the CCT N2 Mapping interface to set the FX-PCA3611 controller’s device type to VND, and reconfigure the N2 supervisor so that it is mapped as a VND device. See N2 Supervisor configuration for more information.

In addition, you must use the CCT N2 Mapping interface to manually create the N2 point mapping table.