Device addressing - Facility Explorer - LIT-12012045 - Field Device - N2 Controllers

Modernization Guide for N2 Controllers - Facility Explorer

Brand
Facility Explorer
Product name
N2 Controllers
Document type
User Guide
Document number
LIT-12012045
Revision date
2019-03-22
Language
English

N2-configured FX-PC controllers support the full range of possible N2 device addresses supported by the N2 protocol standard (1-255); however, BACnet-configured FX-PC controllers only support addresses 4-127. When switching the FX-PC controllers from N2 to BACnet MS/TP, you may need to change your network's device addressing scheme to accommodate this limitation.