Dynamically Creatable: No
Dynamically Deletable: No
|
Property Name |
Required |
Optional |
Proprietary |
Property ID |
Data Type |
Writable |
Range |
|---|---|---|---|---|---|---|---|
|
OBJECT_NAME |
X |
77 |
|||||
|
PRESENT_VALUE |
X |
85 |
X 1 |
||||
|
EFFECTIVE_PERIOD |
X |
32 |
X |
||||
|
SCHEDULE_DEFAULT |
X |
174 |
X |
||||
|
LIST_OF_OBJECT_PROPERTY_REFERENCES |
X |
54 |
X |
||||
|
PRIORITY_FOR_WRITING |
X |
88 |
X |
||||
|
STATUS_FLAGS |
X |
111 |
|||||
|
RELIABILITY |
X |
103 |
|||||
|
OUT_OF_SERVICE |
X |
81 |
X |
||||
|
DESCRIPTION |
X |
28 |
X |
40 characters max |
|||
|
WEEKLY_SCHEDULE |
X |
123 |
X |
||||
|
EXCEPTION_SCHEDULE |
X |
38 |
X |
||||
|
ALARM_STATE |
X |
1006 |
Enumerated |
||||
|
ENABLED |
X |
673 |
Boolean |
X |
|||
|
EXECUTION_PRIORITY |
X |
2197 |
Enumerated |
X |
0–3 |
||
|
ITEM_REFERENCE |
X |
32527 |
Character String |
||||
|
OBJECT_CATEGORY |
X |
908 |
Enumerated |
X |
0–249 |
||
|
STATUS |
X |
512 |
Enumerated |
||||
|
USER_NAME |
X |
2390 |
Character String |
||||
|
PERFORM_INDEX |
X |
965 |
Unsigned |
||||
|
TODAYS_SCHEDULE |
X |
4198 |
List |
1 Writable when OUT_OF_SERVICE is true.