Accumulator - Facility Explorer - LIT-12013685 - F4-XPM04060 - F4-XPM09090 - F4-XPM18000 - F4-XPM

F4-XPM Series Protocol Implementation Conformance Statement

Brand
Facility Explorer
Product name
F4-XPM
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12013685
Revision date
2020-11-11
Language
English

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Accumulator

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

PRESENT_VALUE

X

   

85

 

X 1

 

OUT_OF_SERVICE

X

   

81

 

X

 

STATUS_FLAGS

X

   

111

     

EVENT_STATE

X

   

36

     

OBJECT_NAME

X

   

77

     

SCALE

X

   

187

     

UNITS

X

   

117

 

X

0–65,535

MAX_PRES_VALUE

X

   

65

 

X

0–4,294,967,295

DESCRIPTION

 

X

 

28

 

X

40 characters max

DEVICE_TYPE

 

X

 

31

 

X

20 characters max

RELIABILITY

 

X

 

103

 

X1

 

VALUE_SET

 

X

 

191

 

X

0-4,294,967,295

VALUE_BEFORE_CHANGE

 

X

 

190

     

VALUE_CHANGE_TIME

 

X

 

192

     

PRESCALE

 

X

 

185

 

X

1–65,535 (each part)

LIMIT_MONITORING_INTERVAL

 

X

 

182

 

X

60–604,800

PULSE_RATE

 

X

 

186

 

X1

 

ITEM_REFERENCE

   

X

32527

Character String

   

STATUS

   

X

512

Enumerated

   

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

OBJECT_CATEGORY

   

X

908

Enumerated

X

0–249

ALARM_STATE

   

X

1006

Enumerated

   

OFFLINE

   

X

913

Boolean

   

PERIODIC_UPDATE

   

X

2192

Unsigned

X

1–10,000 value

SAB_MAC_ADDR

   

X

3645

Unsigned

   

DEBOUNCE

   

X

610

Unsigned

X

0-65,535 ms

SLOT

   

X

519

Unsigned

   

USER_NAME

   

X

2390

Character String

   
1 Writable when Out_Of_Service is true.