Dynamically Creatable: No
Dynamically Deletable: No
|
Property Name |
Required |
Optional |
Proprietary |
Property ID |
Data Type |
Writable |
Range |
|---|---|---|---|---|---|---|---|
|
OBJECT_NAME |
X |
77 |
|||||
|
ENABLE |
X |
133 |
X |
||||
|
STATUS_FLAGS |
X |
111 |
|||||
|
EVENT_STATE |
X |
36 |
|||||
|
STOP_WHEN_FULL |
X |
144 |
X |
||||
|
RECORD_COUNT |
X |
141 |
X 1 |
||||
|
TOTAL_RECORD_COUNT |
X |
145 |
|||||
| LOG_BUFFER |
X |
131 |
|||||
|
BUFFER_SIZE |
X |
126 |
|||||
|
DESCRIPTION |
X |
28 |
X |
40 characters max |
|||
|
START_TIME |
X |
142 |
X |
||||
|
STOP_TIME |
X |
143 |
X |
||||
|
NOTIFICATION_THRESHOLD |
X 2 |
137 |
X |
2–100 |
|||
|
RECORDS_SINCE_NOTIFICATION |
X2 |
140 |
|||||
|
LAST_NOTIFY_RECORD |
X2 |
173 |
|||||
|
RELIABILITY |
X |
103 |
|||||
|
ACKED_TRANSITIONS |
X2 |
0 |
|||||
|
EVENT_ENABLE |
X2 |
35 |
X |
||||
| EVENT_MESSAGE_TEXTS_CONFIG |
X2 |
352 |
X |
||||
|
EVENT_MESSAGE_TEXTS |
X2 |
351 | |||||
| EVENT_DETECTION_ENABLE |
X2 |
353 | |||||
|
EVENT_TIME_STAMPS |
X2 |
130 |
|||||
|
NOTIFICATION_CLASS |
X2 |
17 |
X |
1–4,194,302 |
|||
|
NOTIFY_TYPE |
X |
72 |
X |
||||
|
ALARM_STATE |
X |
1006 |
Enumerated |
||||
|
BUFFER_STATE |
X |
2565 |
Enumerated |
||||
|
INTRINSIC_ALARMING_DEFINED |
X |
569 |
Boolean |
X |
|||
|
ENABLED |
X |
673 |
Boolean |
X |
|||
|
EXECUTION_PRIORITY |
X |
2197 |
Enumerated |
X |
0–3 |
||
|
ITEM_REFERENCE |
X |
32527 |
Character String |
||||
|
OBJECT_CATEGORY |
X |
908 |
Enumerated |
X |
0–247 |
||
|
STATUS |
X |
512 |
Enumerated |
||||
|
USER_NAME |
X |
2390 |
Character String |