Calendar - Facility Explorer - LIT-12013127 - FX-PCA4911-0 - FX-PCV1930-0 - Field Device - FX BACnet/IP Controller - FX-PCA49 Advanced Application Programmable Controller - FX-PCV19 Programmable VAV Box Controller

BACnet/IP FX-PCA4911 and FX-PCV1930 Controllers Protocol Implementation Conformance Statement

Brand
Facility Explorer
Product name
FX BACnet/IP Controller
FX-PCA49 Advanced Application Programmable Controller
FX-PCV19 Programmable VAV Box Controller
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12013127
Revision date
2020-11-11
Language
English

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Calendar

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

OBJECT_NAME

X

   

77

     

PRESENT_VALUE

X

   

85

     

DATE_LIST

X

   

23

 

X

 

DESCRIPTION

 

X

 

28

 

X

40 characters max

ALARM_STATE

   

X

1006

Enumerated

   

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

ITEM_REFERENCE

   

X

32527

Character String

   

OBJECT_CATEGORY

   

X

908

Enumerated

X

0–249

STATUS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

Character String

   

GLOBAL_CALENDAR_REFERENCE

   

X

1096

Complex

X

 

GLOBAL_CALENDAR_UPDATE

   

X

1097

Complex

   

DATE_LIST_CHANGED

   

X

1098

Unsigned