Binary Value - BCPro - Facility Explorer - LIT-12012986 - CH-PCX2723-0 - CH-PCX3723-0 - CH-PCX3733-0 - Field Device - FX-PCX17 Expansion Input/Output Module - FX-PCX27 Expansion Input/Output Module - FX-PCX37 Expansion Input/Output Module - FX-PCX47 Expansion Input/Output Module

Programmable Controller Expansion Input/Output Module (PCX) Series Protocol Implementation Conformance Statement

Brand
BCPro
Facility Explorer
Product name
FX-PCX17 Expansion Input/Output Module
FX-PCX27 Expansion Input/Output Module
FX-PCX37 Expansion Input/Output Module
FX-PCX47 Expansion Input/Output Module
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12012986
Revision date
2020-11-11
Language
English

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Binary Value

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

OBJECT_NAME

X

   

77

     

OUT_OF_SERVICE

X

   

81

     

STATUS_FLAGS

X

   

111

     

EVENT_STATE

X

   

36

     

PRESENT_VALUE

X

   

85

 

X

 

INACTIVE_TEXT

 

X

 

46

 

X

40 characters max

ACTIVE_TEXT

 

X

 

4

 

X

40 characters max

COS_TIME

  X 1  

16

     

COS_COUNT

 

X1

 

15

 

X

0–4,294,967,295

STATE_COUNT_RESET

 

X1

 

115

     

ELAPSED_ACTIVE_TIME

 

X1

 

33

 

X

0–4,294,967,295

ACTIVE_TIME_ RESET

 

X1

 

114

     

MIN_OFF_TIME

 

X1

 

66

 

X

0–604,800

MIN_ON_TIME

 

X1

 

67

 

X

0–604,800

PRIORITY_ARRAY

 

X1

 

87

     

RELINQUISH_DEFAULT

 

X1

 

104

 

X

 

CURRENT_COMMAND_PRIORITY

 

X

 

431

     

DESCRIPTION

 

X

 

28

 

X

40 characters max

RELIABILITY

 

X

 

103

 

X 2

 

ALARM_STATE

   

X

1006

Enumerated

   

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

ITEM_REFERENCE

   

X

32527

Character String

   

OBJECT_CATEGORY

   

X

908

Enumerated

X

0–249

ATTRIBUTE_ID

   

X2

3365

Enumerated

   

COMMAND_SIGNATURE

   

X2

3366 Unsigned    

DEFAULT_ATTRIBUTE_VALUE

   

X2

3633

Boolean

   

LAST_RELIABLE_CMD_SIG

   

X2

3362 Unsigned    

PEER_REFERENCE

   

X2

748 Complex

X

 

DIRECTION

   

X2

746

Enumerated

   

ERROR_STATUS

   

X2

576

Enumerated

   

FAILSOFT

   

X2

2567

Boolean

X

 

IN_TEST

   

X2

3368

Boolean

   

CURRENT_CMD_SIG

   

X2

3378 Unsigned    

CURRENT_RELIABILITY

   

X2

3377

Enumerated

   

STANDARD_NAME

   

X2

3670

Enumerated

   

BACNET_EXPOSED

   

X

3807

Boolean

X

 

LAST_RELIABLE_VALUE

   

X2

3369

Boolean

   

DEFAULT_VALUE

   

X2

3113

Boolean

X

 

TEST_VAL

   

X2

3371

Boolean

   

INPUT

   

X2

513

Boolean

   

OUTPUT

   

X2

663

Boolean

   

CURRENT_VALUE

   

X2

3376

Boolean

   

OFFLINE

   

X2

913

Boolean

   

RESTORE_COMMAND_PRIORITY

   

X

721

Bit String

X

 

STATUS

   

X

512

Enumerated

   

STATES_TEXT

   

X

931

Enumerated

 

USER_NAME

   

X

2390

Character String

 
1 Not present in all instances.
2 Not writable in all instances.