The MS/TP bus is subject to a number of physical factors that can affect performance. Consider the following common physical attributes:

  • Check wires.

    • Verify proper wire gauge, connections, polarity, and lengths.

    • Look for opens and shorts.

  • Check terminations.

    • Verify that EOL terminations are only at the ends of daisy chains.

  • Check addresses.

    • Check for duplicate addresses.

    • Verify that the address range is sequential.

  • Check for and eliminate T-Taps (wire configurations that create a T shape) and star configurations.

  • Check for consistent baud rates.

  • Check for sources of interference.