You can use wildcards for Week and Day entries. The Week and Day selection identifies a month, a week of the month, and a day of the week. The possible selections include any (every) as the week of the month, 1 (Days 1–7), 2 (Days 8–14), 3 (Days 15–21), 4 (Days 22–28), 5 (Days 29–31), and 6/Last (the Last seven days). The following table shows some sample wildcard week and day exceptions.

Table 1. Sample Wildcard Week and Day Exceptions

Month

Week of Month

Day of Week

Meaning

any

any

any

Every day of the year

any

1

Days 1–7

Monday

Monday of the first week of every month

Jan

any

Tuesday

Every Tuesday in January

Feb

2

Days 8–14

any

Every day of the week in the second week of February

any

any

Wednesday

Wednesday of every week of every month

Mar

any

any

Every day of every week in March

any

3

Days 15–21

any

Every day of the third week of every month

Apr

4

Days 22–28

Thursday

Thursday in the fourth week of April

any

5

Days 29–31

any

29th, 30th, and 31st (as applicable) of every month

Jun

6/Last

Last seven days

Saturday

Saturday in the last seven days of June