Week and Day - BCPro - LIT-12011905 - Server - BCPro Data Server - 4.0

BCPro Data Server

Brand
BCPro
Product name
BCPro Data Server
Document type
User Guide
Document number
LIT-12011905
Version
4.0
Revision date
2020-03-27
Language
English

You can use a week and day entry when defining exceptions to the weekly schedule. The following table describes the options available for defining a week and day calendar or exception schedule entry (Saturday of the first week in May, for example). Any mixture of any (wildcard) and specified entries is allowed. Week and day entries apply to all years.

Table 1. Week and Day Format

Menu

Options

Month

any, January through December, Odd (odd numbered months, 1 is January, 3 is March, and so on), Even (even numbered months, 2 is February, 4 is April, and so on)

Week of Month

any

1 = Days 1 through 7

2 = Days 8 through 14

3 = Days 15 through 21

4 = Days 22 through 28

5 = Days 29 through 31

6 (Schedule object)/Last (Calendar object) = Last seven days of the month

Day of Week

any, Monday through Sunday

Note: For exception schedule entries, you also need to define the Precedence at which the schedule executes the exception schedule.