Attributes associated with the hardware source for object data are shown under the Hardware tab of the display panel.

Table 1. VND Hardware Tab Attributes

Attribute Name

Data Type

Notes 1

Initial Value

Values/Options/Range

VND Integration Hardware Attributes

Disable Automatic Alarming

True or False

CW

False

 

Protocol Descriptions

Text

C

VendorDriver

 

Protocol Revision

Text

C

   

Protocol Revision Date

Date

C

   

Protocol Revision Time

Time

C

   

Temporary Status Item Expiration Time

Number

CW

 

0–65,535

Units = Seconds

Vendor DLL

Text

CW

VENDOR.DLL

 

Vendor Integration Size

Number

   

Units = bytes

Vendor Revision Data

Date

C

   

Vendor Revision Time

Time

C

   

VND Integration, Device, and Point Hardware Attributes

Vendor Configuration Data

List

CW

 

Maximum characters = 80

Maximum entries = 128

Vendor Reference

Text

C

   

VND Point Hardware Attributes

Field View

Text

   

Applies to only AI, AO, BO, MI, and MO objects.

Interface Value

One from a set

   

Applies to only AI, AO, BO, MI, and MO objects.

Max Value

Real value

CW

250.0 deg F

Applies to only AO objects.

Min Value

Real value

CW

-50.0 deg F

Applies to only AO objects.

Offline

True or False

   

Applies to only AI, AO, BI, BO, MI and MO objects.

Overridden

True or False

   

Applies to only AI, AO, BO, MI, and MO objects.

Priority

Number

CW

 

Applies to only AI, AO, BO, MI, and MO objects.

Trouble

True or False

   

Applies to only BI and BO objects.

1 C - Configurable, W - Writable