Contains the destinations for the Who-Is message sent during the device autodiscovery process. When the list is empty, the object sends a global broadcast in the form of the Who-Is. Adding entries to the list limits the scope of the Who-Is broadcast to only the networks and device instance ranges specified. Multiple entries to this list cause the object to send multiple Who-Is messages sequentially.
Table 1. Device Discovery Range Network Number

Broadcast Type

Network Numbers

Local

0 (locked for editing)

Global

65,535 (locked for editing)

Remote

1–65,534 (editable)