Calendar - BCPro - LIT-12012994 - CH-PCA2513-0 - CH-PCA3613-0 - Field Device - CH-PCA25 Advanced Application Programmable Controller - CH-PCA36 Advanced Application Programmable Controller

Advanced Application Programmable Controllers Protocol Implementation Conformance Statement

Brand
BCPro
Product name
CH-PCA25 Advanced Application Programmable Controller
CH-PCA36 Advanced Application Programmable Controller
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12012994
Revision date
2019-11-19
Language
English

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Calendar

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

OBJECT_NAME

X

   

77

     

DATE_LIST

X

   

23

 

X

 

DESCRIPTION

 

X

 

28

 

X

40 characters max

ALARM_STATE

   

X

1006

Enumerated

   

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

ITEM_REFERENCE

   

X

32527

Character String

   

OBJECT_CATEGORY

   

X

908

Enumerated

X

0–249

STATUS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

Character String

   

GLOBAL_CALENDAR_REFERENCE

   

X

1096

Complex

X

 

GLOBAL_CALENDAR_UPDATE

   

X

1097

Complex

   

DATE_LIST_CHANGED

   

X

1098

Unsigned